Lakewood Instruments

Lakewood Instruments 1240475 Model 1520/30e pH/ORP Water Treatment Controller

No reviews yet
SKU: 1240475
Weight: 1.00 LBS
Shipping: Calculated at Checkout
$1,742.51
icon Share icon Share
  • product-security-image-1.jpg
  • product-security-image-2.jpg
  • product-security-image-3.jpg
  • product-security-image-4.jpg

The Model 1520/30e uses the latest in microprocessor capability, giving the user a high level of application flexibility in pH or ORP control. The user in the field can configure this controller to operate as a pH or an ORP controller. A large illuminated graphics screen, multiple inputs, and very easy setup characterize this new technology. Water meters, sensors and plumbing assemblies are purchased separately. 

Features

  • Removable power cord and receptacles for simple conduit installations.
  • Scheduled feed, which can use three relays for biocides or other chemicals.
  • Two (2) water meter inputs, two (2) drum switch inputs, pH or ORP input, flow switch input, and 4-20 mA output are all standard features.
  • A 4-20 mA Input for remote pH or ORP applications can be used in place of the standard pH or ORP input.
  • Designed with a single circuit board for better reliability and lower cost.
  • Large open shallow enclosure for easy wiring.
  • Heavy-duty stainless steel domed numeric keypad and illuminated graphical display allow for quick and easy programming. Steel domed switches improve the tactile sensing and life expectancy of the keypad.
  • LED indicators for power, alarm and relay status.

Benefits

  • Easy to program with the Lakewood plain English, intuitive, and user friendly menu interface.
  • Controller can be removed from a cooling tower and be placed in another type of application when used with the appropriate pH or ORP sensor.
  • Single circuit board design improves reliability.
  • No add-on options. 4-20 mA output and biocide features are standard.

Specifications

  • pH range: 2-12 pH
  • ORP range: -1000 to +1000 mV
  • Output Signal: One 4 – 20 mA, non-isolated isolated powered output
  • Sensor Types: Solution ground, Signal differential, or Single-Ended
  • Output relays: 4 selectable use
  • Resolution: ± .10 pH or 1 mV
  • Relay ratings: 3A each, 10A total
  • Accuracy & repeatability: ± 1.0%
  • Deadband/Setpoint Adjustable
  • Auto/Manual outputs: Menu selectable
  • Power: 120/240 VAC 50/60 Hz
  • Keypad: 16 tactile push-buttons
  • Ambient: 32° - 120°F (0 - 49°C)
  • Display: Illuminated 128x64 pixel LCD 
  • Enclosure: NEMA 4X, ETL
  • Timer: Relay run time exceeded
  • Drum Switch Inputs: 2 digital contact inputs
  • Water meter inputs (2): Contact head, paddle wheel or turbine

Downloads

Quick Start Guide: Model 1520/30e 

Product Manual: Model 1520/30e

Cut Sheet: Model 1520/30e 

Customers Also Viewed