Neptune
Neptune
Neptune SC-600 Sample Cooler, 316 SS Shell, Inconel 600 Tube Cooler
Checkout securely with:
- Rugged all-welded construction
- Internal baffles to insure maximum heat transfer
- Heat exchange area—one sq. ft.
- Design pressure—3500 psi at 750°F
- 316SS shell construction
- Inconel 600 coil construction
| Material | Pressure Rating | Water Flow Pressure Drop | |||
MODEL | COIL | SHELL | COIL | SHELL | COIL | SHELL |
SC-600 | Inconel 600 | 316SS | 3500 psi | 250 psi | 55 psig @ 250 lbs/hr | 3 psig @3 gpm |
Assuming a coolant inlet of approximately 55°F (12°C) and exit of approximately 120°F (50°C) and a sample exit of approximately 110°F (43°C), the cooler will provide performance approximately per the ranges described below:
HOT WATER SAMPLES:
- At 250°F (120°C), approximately 1500 CC/Min of sample will be produced using 1 gallon per minute of coolant.
- At 700°F (370°C), approximately 950 CC/Min of sample will be produced using 2.5 gallons per minute of coolant.
SATURATED STEAM VAPOR:
The steam sample cooler inlet and exit valves can be used to create various operating pressures in the cooler for producing samples from saturated steam vapor.
- At 175 psia operating pressure, 640 CC/Min of sample can be produced using approximately 3.0 gpm of coolant.
- At 25 psia operating pressure, 300 CC/Min of sample can be produced using approximately 1.5 gpm of coolant.
SUPER HEATED STEAM: Max. sample inlet temperature of 750°F (400°C). (See chart below.)
- 1,000 psia cooler operating pressure produces 640 CC/Min of sample at 3.5 gpm coolant flow.
- 20 psia cooler operating pressure produces 315 CC/Min of sample at 1.75 gpm coolant flow.
Proper installation of the Neptune sample cooler requires valves on sample inlet and cooling water inlet for hot water service. An additional valve must be installed on the sample outlet for all vapor or steam services to obtain required operating pressures in the coil. Proper installation in superheated steam service also requires precooling the sample to 750°F, the maximum design operating temperature of the Neptune Sample Cooler. Precooling can be accomplished by installing a pipe between the main steam header and the sample cooler to radiate excess heat. The length of the pipe is determined from the chart at right.